NYC Admin. Code §§ 24-109, 24-120, 24-122 (Air Pollution Control Code, Title 24, Ch. 1); annual tune-up/combustion-test requirement per Rules of the City of New York Title 15, § 2-09
Under the NYC Air Pollution Control Code (Admin. Code Title 24, Ch. 1), owners of fuel-burning boilers and water heaters must register or obtain a Certificate to Operate from DEP: equipment with a heat input of 350,000 Btu/hr or more (individually, or in the aggregate per building) but less than 4.2 million Btu/hr requires registration (§ 24-109), while equipment at or above 4.2 million Btu/hr requires an operating certificate (§ 24-122); both are valid for up to three years. Separately, under Rules of the City of New York § 2-09, equipment of 2.8 million Btu/hr or more requires annual tune-ups and combustion-efficiency testing, with records kept for at least five years.
15 RCNY Chapter 1 (Asbestos Control Program); NYC Admin. Code Title 24, Subchapter 5 (Asbestos)
15 RCNY Chapters 19.1 and 31 — Unified Stormwater Rule
40 CFR Part 61, Subpart M (§ 61.145) — National Emission Standard for Asbestos (NESHAP)
6 NYCRR Part 613 — Petroleum Bulk Storage
NYC Admin. Code § 24-168.1 (Clean heating oil)
NYC Admin. Code Title 24, Ch. 1, Subch. 8 (Fuel Standards), § 24-168, as amended by Local Law 32 of 2023