NYC · DOHMH

LL77 Cooling Towers

NYC Admin Code § 17-194.1; 24 RCNY Ch. 8; § 28-317

Local Law 77 of 2015 requires any building with a cooling tower or evaporative condenser (no size threshold) to register the device with DOB before operation, maintain a Legionella management plan, and file an annual compliance certification (due Nov 1). Local Law 159 of 2025 (rules effective ~May 2026) tightens sampling to a 31-day (monthly) Legionella culture interval, requires ELAP-certified labs, and raises penalties.

Effective · 2015-08-06
Last amended · 2025-05-07
Status · active
Subject · building safety